York YLCC-H User Manual Page 8

  • Download
  • Add to my manuals
  • Print
  • Page
    / 52
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 7
YCSA
49 to 96 kW
R407C
49
E-COM-C0602
Compatibility table / Codes
YCSA
119 to 156 kW
R410A
Models YCSA 50 TP YCSA 60 TP YCSA 80 TP YCSA 100 TP YCSA 120 TP YCSA 150 TP
Cooling only unit (Pack included) 668524682 668526082 668528082 668521082 668551152 668551502
Heat pump unit (Pack included) 668624682 668626082 668628082 668621082 668651152 668651502
Options (Factory fitted)
Models YCSA 50 T YCSA 60 T YCSA 80 T YCSA 100 T YCSA 120 TP YCSA 150 TP
Cooling only unit (without Pack) 668524680 668526080 668528080 668521080 668551150 668551500
Heat pump unit (without Pack) 668624680 668626080 668628080 668621080 668651150 668651500
Anti-corrosion coated condenser fins (cooling only) 611084646 611086060 611088080 611081010 611081210 611081510
Anti-corrosion coated condenser fins (heat pump) 611085050 611086061 611088081 611081011 611081211 611081511
Copper/copper condenser (cooling only) 611064646 611066060 611068080 611061010 611061210 611061510
Copper/copper condenser (heat pump) 611054646 611056060 611058080 611051010 611051210 611051510
LAK -18ºC for cooling only unit 613112081 STANDARD
Low noise version 613995082 613996086 613998081 613991084 613991285 613991584
Dual Pumps NA NA 613990881 613991085 613991286 613991585
Accessories (Supplied loose)
Mechanical flow switch 611992021
Water Filter * 611300170 611300190
Remote control 613802011
Remote terminal 613802231 613802241
B.M.S. Communication 613802041 613802051
* included with unit version “P” only for unit without pack. Filter size: 2” for YCSA 50-60-80 and 2 1/2” for YCSA 100-120-150.
YCSA / YCSA-H
50 T-TP 60 T-TP 80 T-TP 100 T-TP 120 T-TP 150 T-TP *
Performance Cooling capacity cooling only units (1) kW 49.2 - 47.9 61.2 - 59.3 78.6 - 76.5 96 - 93 119 - 118.4 156 - 153
Total Input Power (1) kW 17.9 - 19.3 23.8 - 25.7 27.4 - 29.7 38.4 - 41.4 43 - 43.6 50 - 53
Cooling capacity heat pump units (1) kW 45.4 - 45.2 65.3 - 63.5 74.3 - 72.2 90 - 87 114 - 110.8 145
Heating capacity heat pump units (1) kW 54.4 - 54.7 62.5 - 64.3 81.2 - 83.4 101 - 104.1 119.6 - 122.7 150
Total Input Power cooling/heating mode (1) (2) kW 18.7 / 19.7 22.2 / 23 28 / 29.6 38.3 / 36.5 43.3 / 39.6 50
Total Input Power cooling/heating mode (1) (3) kW 18.9 / 20 23 / 24.8 30.1 / 31.8 41.3 / 39.6 46.5 / 42.7 53.5
Capacity steps % 0-50-100% 0-25-50-75-100%
Sound power level dB(A) 84 85 88 89 86 88
Sound pressure level at 10 m dB(A) 56 57 60 61 58 60
Sound power level Low Noise version dB(A) 78 79 80 83 82 84
Sound pressure level Low Noise version at 10 m dB(A) 50 51 52 55 54 56
Compressor Type Hermetic Scroll (R407C) Hermetic Scroll (R410A)
Quantity 2 4
Air side heat exchanger Fans quantity 2 3 4
Working Ambient temp. cooling / heating mode
(4) (-18ºC) -10ºC ~ 46ºC / -10ºC ~ 20ºC -18ºC ~ 46ºC / -10ºC ~ 20ºC
Water side heat exchanger
Type Single Plate Heat Exchanger Dual Plate Heat Exchanger
Unit water volume (2) Litres 179 181 274 278 170 179
Pump Type Multistage horizontal pumps
Available pressure (1) (2) kPa 225 263 223 265 200 180
Pressure drop nominal (1) (3)
kPa 39 42 59 60 32 30
Working range water leaving temp. cooling/heating
(5) ºC (-5ºC) 6ºC ~ 15ºC / 30ºC ~ 50ºC
Water connections inch 2" 2 1/2"
Dimensions & Weight H / W / L mm
1
398 / 1004 / 2103 1400 / 1108 / 2943 1582 / 1140 / 3336 2190 / 1101 / 3416 2263 / 1101 / 3770
Weight pack/without pack cooling only kg 624 / 568 706 / 650 870 / 798 1 030 / 964 1 250 / 1 180 1 645 / 1 585
Weight pack/without pack heat pumps kg 636 / 580 720 / 604 890 / 824 1 065 / 1 000 1 280 / 1 220 1 675 / 1 615
Electrical supply Voltage/Phases/Frequency V/ph/hz 400 / 3 / 50+N+E
Running current (max)
(2) A 46.4 57.7 71 91.3 100 109
Technical features
(1) at nominal conditions (2) version P with hydro kit (3) version without hydro kit
(4) -18ºC with LAK option (5) -5ºC with glycol
* Provisional data
Nominal conditions: Cooling capacities in kW given for 7°C water leaving temperature t 5ºC and 35°C ambient temperature
Heating capacities in kW given for 45°C water leaving temperature and 7°C ambient temperature
T Three phases supply P Pack H Heat pump