York MOH 55 User Manual Page 32

  • Download
  • Add to my manuals
  • Print
  • Page
    / 36
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 31
Blower
YUCC-YUHC 18 to 60
R410A
37
E-COM-M0613
Technical features
Options / Accessories
Sizes 18 24 30 36 48 60
Round duct adapter A
Air filter A
Condensate pump A AMP01C AMP02B
Wall mounting kit A AMW42A AMW50A
Floor mounting kit A AMF44B
Low ambient kit only for YUHC O Contact York
O= option (factory fitted) A= accessory (supplied loose)
YUCC - YUHC
Models Sizes 18 24 30 36 48 60
Cooling capacity kW 5.3 7.0 8.8 10.6 14.1 17.6
Heating capacity kW 6.2 8.0 9.4 11.7 15.5 19.9
Compressor Type Rotary Scroll
Refrigerant R410A
Power supply V/Ph/Hz 230 / 1 / 50 + E 380 / 3 / 50 + E
Power input kW 1.9 2.6 3.2 3.7 4.7 6.0
Fuse rating A 16 20 10 16 16 20
Indoor airflow m
3
/h 1 160 1 460 1 920 2 070 2 400 2 800
External static pressure Pa 40 40 70 70 70 100
Sound pressure at 1 m
Indoor dB(A) 35 35 36 38 40 46
Outdoor dB(A) 43 48 55 57 57 58
H (mm) 298 / 695 298 / 860 298 / 960 298 / 960 298 / 1 245 320 / 1 245
Dimensions Ind. / Out. W (mm) 1 000 / 845 1 000 / 895 1 350 / 990 1 350 / 990 1 350 / 940 1 350 / 940
D (mm) 800 / 335 800 / 330 800 / 360 800 / 360 800 / 360 800 / 360
Net weight
Indoor unit kg 36 38 48 48 50 70
Outdoor unit kg 40 55 79 101 101 110
Type of connection Flare
Piping
Diameter
Gas 1/2” 1/2” 5/8” 3/4” 3/4” 3/4”
Liquid 1/4” 1/4” 3/8” 1/2” 1/2” 1/2”
Refrigerant charge g 2 050 2 600 3 100 3 100 4 000 4 200
Max pipe run m 30 30 30 30 30 30
Operating limits - cooling mode mini / maxi +18ºC / +43ºC
Operating limits - heating mode mini / maxi -7ºC / +24ºC
Nominal cooling capacity based on : - Indoor Air Temp. 27°C DB / 19°C WB - Outdoor Air Temp. 35°C DB
Nominal heating capacity based on : - Indoor Air Temp. 21°C DB - Outdoor Air Temp. 7°C DB/6°C WB
Piping length : 7.5 m with initial charge
Page view 31