TABLE 35: DM078 (6-1/2 TON) STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE
1
2
ESP
3
TURNS OPEN
4
012345
CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP
0.2
- - - - - - 3291 1191 1.28 3096 1059 1.14 2963 948 1.02 2757 831 0.89
0.4
- - - 3168 1225 1.31 2969 1085 1.16 2658 939 1.01 2535 834 0.89 2255 718 0.77
0.6
3223 1273 1.37 2732 1084 1.16 2500 947 1.02 2110 803 0.86 1923 699 0.75 1608 596 0.64
0.8
2541 1091 1.17 2168 925 0.99 1882 793 0.85 - - - - - - - - -
1.0
1859 908 0.97 - - - - - - - - - - - - - - -
1.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
2.
Blower performance includes two-inch throwaway filters.
3.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
4.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
5.
W = Watts
TABLE 36: DM078 (6-1/2 TON) OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE
1
2
ESP
3
TURNS OPEN
4
012345
CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP CFM
W
5
BHP
0.4
---------------348915531.67
0.6
- - - - - - - - - - - - 3394 1641 1.76 3101 1407 1.51
0.8
- - - - - - 3623 2009 2.15 3323 1742 1.87 2971 1477 1.58 2607 1241 1.33
1.0
- - - 3643 2150 2.31 3224 1820 1.95 2889 1569 1.68 2466 1306 1.40 2009 1071 1.15
1.2
3613 2238 2.40 3143 1917 2.06 2748 1621 1.74 2369 1385 1.49 1879 1141 1.22 - - -
1.4
3099 2039 2.19 2636 1711 1.83 2195 1424 1.53 - - - - - - - - -
1.6
2586 1833 1.97 2124 1532 1.64 - - - - - - - - - - - -
1.8
2073 1621 1.74 - - - - - - - - - - - - - - -
1.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
2.
Blower performance includes two-inch throwaway filters.
3.
ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been
deducted from the total static pressure of the blower.
4.
“Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.
5.
W = Watts
Page view 36