264973-YIM-A-0806
Unitary Products Group 31
OPTIONAL ELECTRIC HEAT
The factory-installed heaters are wired for single point power
supply. Power supply need only be brought into the single
point terminal block.
These CSA approved heaters are located within the central
compartment of the unit with the heater elements extending
in to the supply air chamber.
Fuses are supplied, where required, by the factory. Some kW
sizes require fuses and others do not. refer to Table 31 for
minimum CFM limitations and to Tables 9 through 28 for elec-
trical data.
OPTIONAL GAS HEAT
These gas-fired heaters have aluminized-steel or optional
stainless steel, tubular heat exchangers with spark ignition.
GAS PIPING
Proper sizing of gas piping depends on the cubic feet per
hour of gas flow required, specific gravity of the gas and the
length of run. "National Fuel Gas Code" Z223.1 (in U.S.A.) or
the current Gas Installation Codes CSA-B149.1 (in Canada)
should be followed in all cases unless superseded by local
codes or gas utility requirements. Refer to the Pipe Sizing
Table 33. The heating value of the gas may differ with locality.
The value should be checked with the local gas utility.
NOTE: There may be a local gas utility requirement specify-
ing a minimum diameter for gas piping. All units
require a one-inch pipe connection at the entrance
fitting.
TABLE 31: MINIMUM SUPPLY AIR CFM
Heater Unit Model Size (Nominal Tons)
kW Voltage
078 (6.5) 090 (7.5) 102 (8.5) 120 (10) 150 (12.5)
Minimum Supply Air CFM
9
208/
230
1950 2250 2550 - -
18 1950 2250 2550 3000 3750
24 1950 2250 2550 3000 3750
36 1950 2250 2550 3000 3750
54 - - - 3000 3750
9
480
1950 2250 2550 - -
18 1950 2250 2550 3000 3750
24 1950 2250 2550 3000 3750
36 1950 2250 2550 3000 3750
54 - - - 3000 3750
9
600
1950 2250 2550 - -
18 1950 2250 2550 3000 3750
24 1950 2250 2550 3000 3750
36 1950 2250 2550 3000 3750
54 - - - 3000 3750
TABLE 32: GAS APPLICATION DATA
Unit
Input (MBH) Output (MBH)
Temp Rise
(°F)
Size Opt.
078
10 120 96 20-50
15 180 144 35-65
090
10 120 96 15-45
15 180 144 30-60
102
10 120 96 15-45
15 180 144 30-60
120
15 180 144 20-50
20 240 192 30-60
150
15 180 144 10-40
20 240 192 20-50
FIGURE 21 - SIDE ENTRY GAS PIPING
FIGURE 22 - BOTTOM ENTRY GAS PIPING
O P T I O N A L
C O I L
G U A R D
S H O W N
OPTIONAL
COIL
GUARD
SHOWN