FORM 160.55-O1 (402)
101
YORK INTERNATIONAL
“OIL - HIGH DIFFERENTIAL PRESSURE”
The differential oil Pressure increased to > 60.0 PSID
while the oil pump was running. The differential oil
pressure is the difference between the output of the
Sump Oil Pressure Transducer (system low pressure)
and the output of the Pump Oil Pressure Transducer
(system high pressure). The chiller can be started after
the differential oil pressure decreases to < 60.0 PSID
and the COMPRESSOR switch is placed in the Stop-
reset (O) position.
“CONTROL PANEL – POWER FAILURE”
A Control Power failure has occurred. If the power fail-
ure duration was < the duration of the applicable
“Coastdown” period (2.5 minutes standard; 15 minutes
steam turbine), the remainder of the “Coastdown” is
performed upon restoration of power. The chiller can
be started after the COMPRESSOR switch is placed
in the Stop-reset (O) position. This message can indi-
cate a Cycling (auto-restart after power failure) or Safety
(manual restart after power failure) shutdown, depend-
ing upon Control Center configuration. It indicates a
Cycling shutdown when displayed in orange characters;
Safety shutdown when displayed in red characters. The
OptiView Control center is configured for auto-restart
or manual restart after power failure by a qualified Ser-
vice technician following instructions in YORK Service
Manual 160.55-M1.
“MOTOR OR STARTER – CURRENT
IMBALANCE”
The Motor Starter detected that the three phase com-
pressor motor current imbalance was > 30% continu-
ously for 45 seconds. The imbalance is not checked
until the chiller has been running for at least 45 seconds
and the average of the three phases of motor current is
> 80% of the programmed 100% chiller Full Load Amps.
The average is calculated as: Iave = (Ia+Ib+Ic) 3.
The imbalance is calculated as:
(Ia-Iave) + (Ib-Iave) + (Ic-Iave)
x 100
2(Iave)
“WATCHDOG – SOFTWARE REBOOT”
The Microboard’s software Watchdog initiated a Mi-
croprocessor reset because it detected that a portion of
the chiller operating Program was not being executed.
The result of this reset is a Safety shutdown and re-
initialization of the Program. This is generally indicative
of a severe electrical power disturbance or impending
Microboard Failure. The chiller can be started after the
COMPRESSOR switch is placed in the Stop-Reset
(O) position.
“SURGE PROTECTION – EXCESS SURGE”
(Flash Memory Card version C.MLM.02.02.xxx
and later)
(Applies only if Surge Protection SHUTDOWN fea-
ture is Enabled) The Surge Window Count surge events
exceeded the Count Limit setpoint. If the Surge Protec-
tion Extended Run feature is Disabled, the chiller
shutsdown as soon as the count exceeds the limit. If the
Extended Run feature is Enabled, this shutdown occurs
only if the count exceeds the limit at completion of the
10 minute Extended Run period. The chiller can be
started after the COMPRESSOR Switch is placed in
the Stop-Reset (O) position.
MOD “B” SOLID STATE STARTER
SAFETY SHUTDOWN MESSAGES
“LCSSS SHUTDOWN – REQUESTING FAULT
DATA...”
The Liquid Cooled Solid State Starter Logic/Trigger Board
has shut down the chiller but the Control Center has not
yet received the cause of the fault from the LCSSS, via
the serial communications link. The LCSSS shuts down
the chiller by opening the Motor Controller LCSSS Stop
Contacts (K1 relay located on the Logic/Trigger Board
and connected between TB6-16 and TB6-53 in the Con-
trol Center). The Microboard, in the Control Center, then
sends a request for the cause of the fault to the Logic/
Trigger Board over the serial communications link. Since
serial communications are initiated every 2 seconds, this
message is typically displayed for a few seconds and then
replaced with the one of the below listed fault messages.
“LCSSS – HIGH INSTANTANEOUS CURRENT”
The Liquid Cooled Solid State Starter Logic/Trigger
Board detected that the compressor motor current in
any phase exceeded 1.1(1.414xRMS value of the pro-
grammed Start Current) for a minimum of 1 second.
The chiller can be started after the COMPRESSOR
switch is placed in the Stop-Reset (O) position.
“LCSSS – HIGH TEMPERATURE PHASE X –
RUNNING”
The Liquid Cooled Solid State Starter Logic/Trigger
Board has detected the temperature of phase A, B or C
(designed as X in the message) Silicon Controlled Rec-
tifier (SCR) Modules has exceeded 212°F while the
chiller was running. The safety can be reset after all
SCR temperatures are < 210°F and the COMPRES-
SOR switch is placed in the Stop-Reset position (O).
However, the chiller cannot be started until all SCR tem-
peratures are < 109°F. During the shutdown, the starter
cooling pump runs until the temperature is < 109°F.
2