14 Johnson Controls Unitary Products
246750-YTG-L-0408
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
NOTE: KW RATING IS FOR OUTDOOR AND INDOOR UNITS.
LOW CFM
COOLING PERFORMANCE DATA - LOW CFM 1-STAGE OPERATION
OUTDOOR UNIT MODEL NO. YZE03611
INDOOR COIL MODEL NO. FC/MC48C + MV16C
CONDENSER
ENTERING AIR
TEMPERATURE
ID CFM 750 800 850
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 57 62 62 67 72 57
65
T.C. 24.3 26.1 25.5 28.1 31.9 24.8 26.4 25.9 28.5 32.2 25.3 26.6 26.3 28.8 32.5
S.C. 23.9 22.4 18.5 19.1 15.6 24.4 22.8 19.1 19.5 16.2 24.9 23.2 19.7 19.9 16.8
K.W. 1.3 1.3 1.3 1.3 1.2 1.3 1.3 1.3 1.2 1.2 1.3 1.3 1.3 1.2 1.2
75
T.C. 23.2 24.9 24.5 27.0 30.6 23.7 25.2 24.8 27.3 30.9 24.2 25.4 25.2 27.6 31.1
S.C. 22.8 21.6 18.1 18.5 15.3 23.3 22.1 18.7 19.0 15.8 23.8 22.6 19.2 19.5 16.3
K.W. 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.5 1.4 1.5 1.5 1.5 1.5 1.4
85
T.C. 22.1 23.6 23.4 25.9 29.4 22.6 23.9 23.7 26.2 29.5 23.1 24.2 24.1 26.4 29.7
S.C. 21.7 20.8 17.7 17.9 15.0 22.2 21.4 18.2 18.5 15.4 22.7 22.0 18.8 19.1 15.8
K.W. 1.8 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7 1.7
95
T.C. 21.0 22.3 22.4 24.8 28.1 21.5 22.7 22.6 25.0 28.2 21.9 23.0 22.9 25.2 28.3
S.C. 20.7 20.0 17.3 17.3 14.6 21.1 20.7 17.8 18.0 15.0 21.6 21.4 18.3 18.7 15.4
K.W. 2.0 2.0 2.0 2.0 1.9 2.0 2.0 2.0 1.9 1.9 2.0 2.0 2.0 1.9 1.9
105
T.C. 19.8 20.9 20.9 23.1 26.1 20.3 21.2 21.1 23.3 26.2 20.7 21.6 21.4 23.5 26.4
S.C. 19.5 19.1 16.3 16.6 13.9 20.0 19.8 16.9 17.3 14.2 20.4 20.4 17.4 18.0 14.5
K.W. 2.3 2.3 2.3 2.3 2.2 2.3 2.3 2.3 2.3 2.2 2.3 2.3 2.3 2.3 2.2
115
T.C. 18.7 19.5 19.4 21.5 24.2 19.1 19.8 19.6 21.7 24.3 19.5 20.2 19.9 21.9 24.5
S.C. 18.4 18.3 15.4 16.0 13.3 18.8 18.9 16.0 16.6 13.5 19.2 19.4 16.5 17.3 13.7
K.W. 2.7 2.6 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.6 2.5
125
T.C. 17.5 18.0 18.0 19.9 22.3 17.9 18.4 18.2 20.1 22.5 18.3 18.7 18.3 20.3 22.6
S.C. 17.3 17.4 14.4 15.4 12.6 17.7 18.0 15.0 16.0 12.8 18.1 18.5 15.7 16.6 12.9
K.W. 3.0 3.0 3.0 2.9 2.9 3.0 3.0 3.0 2.9 2.9 3.0 2.9 2.9 2.9 2.9
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Air Handler Coil
T.C. S.C. KW
AV36 1.00 1.00 1.00
AV48 1.00 1.00 1.00
MV12B FC/MC35B 0.98 0.98 1.00
MV12B FC/MC42B 0.98 0.98 1.00
MV16C FC/MC48C 1.00 1.00 1.00
MV12D FC/MC48D 0.99 1.00 1.00
Variable Speed
Furnace
Coil
T.C. S.C. KW
P(C,V)9*B12 FC/MC/PC35B 0.92 0.89 0.98
PV8*B16 FC/MC/PC35B 0.92 0.89 0.98
P(C,V)9*C16 FC/MC/PC35C 0.92 0.89 0.98
PV8*C16 FC/MC/PC35C 0.92 0.89 0.98
PV8*C20 FC/MC/PC35C 0.92 0.89 0.98
P(C,V)9*C20 FC/MC/PC35C 0.92 0.89 0.98
PV8*B16 FC/MC/PC42B 0.92 0.89 0.98
P(C,V)9*B12 FC/MC/PC42B 0.98 1.05 1.02
P(C,V)9*C20 FC/MC/PC42C 0.92 0.89 0.98
P(C,V)9*C16 FC/MC/PC42C 0.92 0.89 0.98
PV8*C16 FC/MC/PC42C 0.98 1.05 1.02
PV8*C20 FC/MC/PC42C 0.98 1.05 1.02
P(C,V)9*C20 FC/MC/PC48C 0.97 0.93 0.98
P(C,V)9*C16 FC/MC/PC48C 0.97 0.93 0.98
PV8*C16 FC/MC/PC48C 1.00 1.08 1.00
PV8*C20 FC/MC/PC48C 1.01 1.09 1.00
P(C,V)9*D20 FC/MC/PC48D 1.00 1.07 1.00
PV8*C16 HC42 0.97 0.93 0.98
PV8*C20 HC42 0.97 0.93 0.98
PV8*B16 UC42B 0.97 0.93 0.98
P(C,V)9*B12 UC42B 0.97 0.93 0.98
PV8*C20 UC42C 0.97 0.93 0.98
PV8*C16 UC42C 0.97 0.93 0.98
P(C,V)9*C16 UC42C 0.97 0.93 0.98
P(C,V)9*C20 UC42C 0.97 0.93 0.98
P(C,V)9*C20 UC48C 0.97 0.93 0.98
PV8*C20 UC48C 0.97 0.93 0.98
PV8*C16 UC48C 0.97 0.93 0.98
P(C,V)9*C16 UC48C 0.97 0.93 0.98
P(C,V)9*D20 UC48D 0.97 0.93 0.98
Variable Speed
Furnace
Coil
T.C. S.C. KW