York YK145.00-EG4 User Manual Page 6

  • Download
  • Add to my manuals
  • Print
  • Page
    / 28
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 5
6 Johnson Controls
Technical Guide: YK145.00-EG4 (309) Water Source Heat Pumps
PHYSICAL DATA
Model Series 007 009 012 018 024 030 036 042 048 060 070
Nominal Cooling (Ton)
1
0.5 0.75 1.0 1.5 2.0 2.5 3 3.5 4 5 6
Compressor-Type Rotary Reciprocating Scroll
Air Coil-Type Enhanced Copper tubes, Enhanced Aluminum Fins
Face Area(sq ft) 1.17 1.17 1.33 2.56 2.88 2.88 3.47 4.44 4.44 6.11 6.11
Rows/FPI 3/13 3/13 3/15 3/15 3/15 3/15 3/15 3/15 3/15 3/15 3/15
Water Coil-Type Enhanced Surface Co-Axial
Water Connection (in) 1/2 1/2 1/2 3/4 3/4 3/4 3/4 3/4 3/4 1 1
Standard Blower/Motor DWDI Forward-Curved Centrifugal / PSC Direct-Drive
Diameter x Width (in) 6x5 6x5 6x6 9x7 9x7 10x7T 10x7T 11x8T 11x8T 11x10T 11x10T
Motor HP 0.10/3 0.10/3 0.13/3 0.17/3 0.25/3 0.33/3 0.50/3 0.50/3 0.75/3 1.0/3 1.0/3
RSH Filter
Quantity-Size(in)
1-12x16 1-12x16 1-12x20 1-18x24 1-18x24 1-18x24 2-14x20 2-18x20 2-18x20 2-22x22 2-22x22
RSV Filter
Quantity-Size(in)
1-12x20 1-12x20 1-12x20 1-18x24 1-20x25 1-20x25 1-24x24 2-14x25 2-14x25 2-16x30 2-16x30
RSH Cabinet Weight (lb) 130 135 145 195 210 215 240 310 320 370 385
RSV Cabinet Weight (lb) 120 125 135 185 200 210 230 305 315 375 390
NOTE:
1) Nominal Capacity calculated in accordance with ARI / ISO Standard 13256-1 for Water Loop Application
OPERATING LIMITS*
COOLING HEATING
Min. Entering Water 30°F20°F
Max. Entering Water 110°F90°F
*Units are capable of operation with an entering fluid temperature
range of 20°F to 110°F
Page view 5
1 2 3 4 5 6 7 8 9 10 11 ... 27 28

Comments to this Manuals

No comments