4 Unitary Products Group
345094-YTG-D-0108
COOLING CAPACITY - With Air Handler Coils
UNIT
MODEL
AIR HANDLER
COIL
1
MODEL
COOLING
MODEL W STAGE
RATED
CFM
NET MBH
SEER EER
TOTAL SENSIBLE
18 SEER HP WITH MV - VARIABLE SPEED
YZH02411
MV12B 17 FC/MC43B
1 645 18.2 13.5
16.40
14.00
2 835 23.6 18.8 13.60
MV12D 24 FC/MC48D
1 645 18.5 14.0
17.00
14.50
2 835 24.0 19.5 14.00
MV12D 24 FC/MC60D
1 645 18.5 14.0
17.00
14.50
2 835 24.0 19.5 14.00
YZH03611
MV16C 21 FC/MC43C
1 775 24.8 18.2
17.10
14.20
2 1200 35.4 26.6 13.10
MV16C 21 FC/MC48C
1 775 25.0 18.6
17.30
14.40
2 1200 35.8 26.8 13.35
MV12D 24 FC/MC48D
1 845 24.8 18.0
17.35
14.45
2 1245 35.2 26.2 13.35
MV12D 24 FC/MC60D
1 845 24.8 18.3
17.50
14.60
2 1245 35.4 26.4 13.35
MV12D 24 FC/MC62D
1 845 25.6 19.7
18.00
15.00
2 1245 36.0 27.8 13.35
YZH04811
MV16C 21 FC/MC48C
1 1000 33.4 25.0
16.65
13.60
2 1600 46.5 35.6 12.20
MV20D 24 FC/MC48D
1 1045 33.4 25.0
16.30
13.35
2 1570 46.5 35.6 12.05
MV20D 24 FC/MC60D
1 1045 33.0 25.0
16.20
13.25
2 1570 47.0 36.4 12.25
MV20D 24 FC/MC62D
1 1045 33.8 25.8
17.00
13.90
2 1570 47.0 36.6 12.50
YZH06011
MV20D 24 FC/MC60D
1 1175 39.5 27.6
14.75
12.20
2 1820 57.0 42.0 11.35
MV20D 24 FC/MC62D
1 1175 41.0 29.8
15.50
12.80
2 1820 57.0 43.0 11.80
18 SEER HP WITH AV/SV - VARIABLE SPEED
YZH02411 AV36 21
- 1 600 18.1 13.5
16.65
14.20
2 765 23.4 18.5 13.70
YZH03611
AV36 21
- 1 830 25.2 19.0
17.45
14.55
2 1270 35.4 27.4 13.40
AV/SV48 24
- 1 910 25.8 20.4
17.65
14.70
2 1190 35.4 27.0 13.60
YZH04811
AV/SV48 24
-
1 1135 34.0 26.4
16.75
13.70
2 1610 47.0 36.4 12.30
AV/SV60 24
- 1 1085 33.6 26.0
16.55
13.55
2 1655 47.0 37.0 12.30
YZH06011 AV/SV60 24
- 1 1145 40.5 29.0
15.15
12.50
2 1765 56.5 41.5 11.50
Rated in accordance with DOE test procedures (Federal Register 12-27-79 and 3-18-88) and ARI Standards 210.
Cooling MBH based on 80°F entering air temperature, 50% RH, and rated air flow.
EER (Energy Efficiency Ratio) is the total cooling output in BTU’s at 95°F outdoor ambient divided by the total electric power in watt-hours at those conditions.
SEER (Seasonal Energy Efficiency Ratio) is the total cooling output in BTU’s during a normal annual usage period for cooling divided by the total electric power
input in watt-hours during the same period.
1. MC coils available with a factory installed horizontal drain pan. See price pages for specific model number.
Page view 3