YORK INTERNATIONAL
FORM 160.81-EG1
collecting the data, but the oldest data drops off the
graph from left to right at the next data collection inter-
val. For ease of identification, each plotted parameter,
title and associated Y-axis labeling is color coordinated.
Display Only:
This screen allows the user to view the graphical
trending of the selected parameters and is a gate-
way to the graph setup screens.
Programmable:
Start
Stop
y-axis
x-axis
The TREND SETUP screen is used to configure the
trending screen. The parameters to be trended are se-
lected from the Trend Common Slots screen, accessed
from the Slot Numbers button or the Master Slot Num-
bers List found in the Operating Manual. The interval at
which all the parameters are sampled is selected under
the Collection Interval button. The data point minimum
and maximum values may be adjusted closer to in-
crease viewing resolution.
Programmable:
Chart Type (select continuous or one screen)
Collection Interval
Select
Data Point Slot Number (1 - 6)
Data Point Min. (1 - 6)
Data Point Max (1 - 6)
The TREND COMMON SLOTS screen displays the
Master Slot Numbers List of the monitored parameters.
Display Only:
Slot Numbers
Programmable:
Page Up
Page Down
Print
DISPLAY MESSAGES
The Control Center continuously monitors the operat-
ing system, displaying and recording the cause of any
shutdowns (Safety, Cycling or Normal). The condition
of the chiller is displayed at the System Status line that
contains a message describing the operating state of
the chiller; whether it is stopped, running, starting or
shutting down. A System Details Line displays Warn-
ing, Cycling, Safety, Start Inhibit and other messages
that provide further details of the Status Bar messages.
Messages are color-coded: Green – Normal Operations;
Yellow – Warnings; Orange – Cycling Shutdowns; and
Red – Safety Shutdowns to aid in identifying problems
quickly.
Status messages include:
System Ready To Start
Cycling Shutdown – Auto Restart
Safety Shutdown – Manual Restart
Start Sequence Initiated
System Run (with countdown timers)
Start Inhibit
Slide Valve Closing Before Shutdown
System Lockout Delay
Run Messages include:
Leaving Chilled Liquid Control
Motor Pulldown Limit
Motor – High Current Limit
Start Inhibit Messages include:
Anti-Recycle XX min/sec.
Slide Valve – Position >30%
Motor Current >15% FLA
LCSSS – High-Temperature Phase X - Stopped
Warning Messages include:
Real Time Clock Failure
Setpoint Override
Condenser – High Pressure Limit
Evaporator – Low Pressure Limit
Freeze Threat From Operating Chiller
Freeze Threat, Condenser Flow Switch Open
Low Discharge Superheat Limit