York YCJD18 User Manual Page 14

  • Download
  • Add to my manuals
  • Print
  • Page
    / 18
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 13
364834-YTG-C-0708
14 Johnson Controls Unitary Products
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between 73-87 F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the
listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.
COOLING PERFORMANCE DATA
AIR CONDITIONER MODEL NO. YCJD36S41S1(H)
INDOOR COIL MODEL NO. FC/MC/PC43
CONDENSING
ENTERING AIR
TEMPERATURE
IDCFM 1000 1200 1400
ID DB (°F) 80 80 75 80 80 80 80 75 80 80 80 80 75 80 80
ID WB (°F) 57 62 62 67 72 57 62 62 67 72 57 62 62 67 72
65
T.C. 34.7 36.1 35.2 37.4 37.3 33.8 35.5 34.8 37.0 37.5 32.9 34.9 34.4 36.6 37.6
S.C. 34.3 33.0 27.6 25.5 18.4 33.3 31.0 26.2 24.6 18.0 32.3 29.1 24.7 23.6 17.7
KW 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 2.0 1.9 2.0 1.9 2.0 2.0
75
T.C. 33.6 34.7 33.6 35.9 36.6 32.6 33.9 33.2 35.5 36.6 31.5 33.2 32.7 35.1 36.6
S.C. 33.3 32.5 27.5 25.6 18.6 32.1 30.6 25.8 24.5 18.0 31.0 28.7 24.2 23.3 17.5
KW 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.2 2.1 2.2 2.2 2.2 2.2
85
T.C. 32.4 33.2 32.0 34.4 35.8 31.3 32.3 31.5 34.1 35.7 30.2 31.5 31.0 33.7 35.5
S.C. 32.2 32.0 27.3 25.8 18.8 30.9 30.2 25.5 24.3 18.0 29.6 28.3 23.7 22.9 17.3
KW 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.4 2.3 2.4 2.4 2.4 2.4
95
T.C. 31.3 31.7 30.4 33.0 35.0 30.1 30.7 29.9 35.0 34.8 28.9 29.8 29.4 32.2 34.5
S.C. 31.1 31.5 27.2 26.0 19.0 29.7 29.7 25.2 24.9 18.0 28.3 27.9 23.2 22.5 17.1
KW 2.6 2.6 2.6 2.6 2.7 2.6 2.6 2.6 2.6 2.7 2.5 2.6 2.6 2.6 2.6
105
T.C. 27.9 28.8 27.2 29.8 32.5 27.0 27.8 26.6 29.4 32.2 26.0 26.9 25.9 29.0 31.9
S.C. 28.7 28.9 25.0 25.0 18.4 27.3 27.2 23.2 23.2 17.3 25.8 25.6 21.5 21.4 16.2
KW 2.8 2.8 2.8 2.8 2.9 2.8 2.8 2.8 2.8 2.9 2.7 2.8 2.7 2.8 2.9
115
T.C. 24.6 26.0 24.2 26.8 30.1 23.9 25.1 23.4 26.3 29.8 23.3 24.1 22.6 25.9 29.5
S.C. 26.3 26.3 22.8 24.1 17.8 24.9 24.8 21.3 22.2 16.6 23.5 23.3 19.8 20.3 15.4
KW 3.0 3.0 3.0 3.0 3.1 3.0 3.0 2.9 3.0 3.1 2.9 2.9 2.9 3.0 3.1
125
T.C. 21.3 23.2 21.1 23.7 27.6 20.9 22.3 20.2 23.2 27.3 20.5 21.3 19.3 22.7 27.0
S.C. 23.9 23.8 20.6 23.2 17.2 22.5 22.4 19.4 21.2 15.9 21.1 21.0 18.2 19.2 14.6
KW 3.2 3.2 3.2 3.2 3.4 3.2 3.2 3.1 3.2 3.3 3.1 3.1 3.1 3.2 3.3
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Air Handler Coil T.C. S.C. KW
FC/MC/PC43 1.00 1.00 1.00
FC/MC/PC48 1.00 1.00 1.00
HC42 1.00 1.00 1.00
UC48 1.00 1.00 1.00
AHP36 1.00 1.00 1.00
AHP42 1.00 1.00 1.00
AV36 1.01 1.01 0.92
MV16C FC/MC43C 1.01 1.02 0.92
MA12B FC/MC43B 1.00 1.00 1.00
MV16C FC/MC48C 1.01 1.02 0.92
MV20D FC/MC48D 1.01 1.03 0.92
MA14D FC/MC48D 1.00 1.00 1.00
MV12D FC/MC48D 1.01 1.02 0.92
F5FP048 1.00 1.00 1.00
Variable Speed
Furnace
Coil T.C. S.C. KW
PV8*A12 FC/MC/PC37A 1.00 1.00 0.91
PV9*A12 FC/MC/PC37A 1.00 1.00 1.00
PV8*B16 FC/MC/PC43B 1.01 1.01 0.92
PV8*C16 FC/MC/PC43C 1.01 1.02 0.92
PV8*C20 FC/MC/PC43C 1.01 1.01 0.92
P(C,V)9*B12 FC/MC/PC43B 1.00 1.01 0.91
P(C,V)9*C16 FC/MC/PC43C 1.01 1.01 0.92
P(C,V)9*C20 FC/MC/PC43C 1.01 1.01 0.92
PV8*C16 FC/MC/PC48C 1.01 1.02 0.92
PV8*C20 FC/MC/PC48C 1.01 1.01 0.92
P(C,V)9*C16 FC/MC/PC48C 1.01 1.02 0.92
P(C,V)9*C20 FC/MC/PC48C 1.01 1.01 0.92
P(C,V)9*D20 FC/MC/PC48D 1.01 1.02 0.92
PV8*C16 HC42 1.01 1.02 0.92
PV8*C20 HC42 1.01 1.01 0.92
P(C,V)9*C16 HC42 1.01 1.01 0.92
P(C,V)9*C20 HC42 1.01 1.01 0.92
Page view 13
1 2 ... 9 10 11 12 13 14 15 16 17 18

Comments to this Manuals

No comments